Full metadata record
DC poleHodnotaJazyk
dc.contributor.authorKadlečíková, M.
dc.date.accessioned2021-01-04T08:47:41Z
dc.date.available2021-01-04T08:47:41Z
dc.date.issued2020
dc.identifier.citationElectroscope. 2020, č. 1.cs
dc.identifier.issn1802-4564
dc.identifier.urihttp://147.228.94.30/images/PDF/Rocnik2020/Cislo1_2020/r14c1c5.pdf
dc.identifier.urihttp://hdl.handle.net/11025/42298
dc.description.sponsorshipWe are grateful to the scientific grant agency VEGA of the Ministry of Education, Science, Research and Sport of the Slovak Republic for financial support of project No. 1/0532/19 and to the Slovak Research and Development Agency, contract No.APVV-17-0169.en
dc.format6 s.cs
dc.format.mimetypeapplication/pdf
dc.language.isoenen
dc.publisherZápadočeská univerzita v Plzni, Fakulta elektrotechnickács
dc.rights© 2020 Electroscopeen
dc.subjectRamanova analýzacs
dc.subjectexperimentcs
dc.subjectdetekce poruchycs
dc.subjectolejcs
dc.subjectRamanova spektroskopiecs
dc.titleTransformer fault detection based on Raman analysis of the transformer oil (A case study)en
dc.typečlánekcs
dc.typearticleen
dc.rights.accessopenAccessen
dc.type.versionpublishedVersionen
dc.description.abstract-translatedThe paper reports on an experiment in the academic laboratory that aimed to detect a transformer fault by Raman spectroscopy of the transformer oil. Indicators of oil degradation (eg gases, sludge, cellulose) could not be detected. Combustion indicators (soot – graphitic particles, graphene particles, amorphous carbon) in the transformer oil were reliably detected by Raman measurements. The transformer was disassembled at the factory. It was shown that the magnetic core and electrical circuit of the transformer were irreversibly damaged and the contamination of the active parts of the transformer and the oil was massive. Two interturn short circuits were detected. It was confirmed that in the place of the coil shorts, where an electric arc burned, melting occurred of the winding conductors and of a part of the transformer core. Raman spectroscopy proved to be a useful method for rapid diagnostics of the events in a hermetically sealed transformer vessel.en
dc.subject.translatedRaman analysisen
dc.subject.translatedexperimenten
dc.subject.translatedfault detectionen
dc.subject.translatedoilen
dc.subject.translatedRaman spectroscopyen
dc.type.statusPeer-revieweden
Vyskytuje se v kolekcích:Číslo 1 (2020)
Číslo 1 (2020)

Soubory připojené k záznamu:
Soubor Popis VelikostFormát 
r14c1c5.pdfPlný text677,17 kBAdobe PDFZobrazit/otevřít


Použijte tento identifikátor k citaci nebo jako odkaz na tento záznam: http://hdl.handle.net/11025/42298

Všechny záznamy v DSpace jsou chráněny autorskými právy, všechna práva vyhrazena.