Full metadata record
DC pole | Hodnota | Jazyk |
---|---|---|
dc.contributor.author | Kadlečíková, M. | |
dc.date.accessioned | 2021-01-04T08:47:41Z | |
dc.date.available | 2021-01-04T08:47:41Z | |
dc.date.issued | 2020 | |
dc.identifier.citation | Electroscope. 2020, č. 1. | cs |
dc.identifier.issn | 1802-4564 | |
dc.identifier.uri | http://147.228.94.30/images/PDF/Rocnik2020/Cislo1_2020/r14c1c5.pdf | |
dc.identifier.uri | http://hdl.handle.net/11025/42298 | |
dc.description.sponsorship | We are grateful to the scientific grant agency VEGA of the Ministry of Education, Science, Research and Sport of the Slovak Republic for financial support of project No. 1/0532/19 and to the Slovak Research and Development Agency, contract No.APVV-17-0169. | en |
dc.format | 6 s. | cs |
dc.format.mimetype | application/pdf | |
dc.language.iso | en | en |
dc.publisher | Západočeská univerzita v Plzni, Fakulta elektrotechnická | cs |
dc.rights | © 2020 Electroscope | en |
dc.subject | Ramanova analýza | cs |
dc.subject | experiment | cs |
dc.subject | detekce poruchy | cs |
dc.subject | olej | cs |
dc.subject | Ramanova spektroskopie | cs |
dc.title | Transformer fault detection based on Raman analysis of the transformer oil (A case study) | en |
dc.type | článek | cs |
dc.type | article | en |
dc.rights.access | openAccess | en |
dc.type.version | publishedVersion | en |
dc.description.abstract-translated | The paper reports on an experiment in the academic laboratory that aimed to detect a transformer fault by Raman spectroscopy of the transformer oil. Indicators of oil degradation (eg gases, sludge, cellulose) could not be detected. Combustion indicators (soot – graphitic particles, graphene particles, amorphous carbon) in the transformer oil were reliably detected by Raman measurements. The transformer was disassembled at the factory. It was shown that the magnetic core and electrical circuit of the transformer were irreversibly damaged and the contamination of the active parts of the transformer and the oil was massive. Two interturn short circuits were detected. It was confirmed that in the place of the coil shorts, where an electric arc burned, melting occurred of the winding conductors and of a part of the transformer core. Raman spectroscopy proved to be a useful method for rapid diagnostics of the events in a hermetically sealed transformer vessel. | en |
dc.subject.translated | Raman analysis | en |
dc.subject.translated | experiment | en |
dc.subject.translated | fault detection | en |
dc.subject.translated | oil | en |
dc.subject.translated | Raman spectroscopy | en |
dc.type.status | Peer-reviewed | en |
Vyskytuje se v kolekcích: | Číslo 1 (2020) Číslo 1 (2020) |
Soubory připojené k záznamu:
Soubor | Popis | Velikost | Formát | |
---|---|---|---|---|
r14c1c5.pdf | Plný text | 677,17 kB | Adobe PDF | Zobrazit/otevřít |
Použijte tento identifikátor k citaci nebo jako odkaz na tento záznam:
http://hdl.handle.net/11025/42298
Všechny záznamy v DSpace jsou chráněny autorskými právy, všechna práva vyhrazena.