Název: Transformer fault detection based on Raman analysis of the transformer oil (A case study)
Autoři: Kadlečíková, M.
Citace zdrojového dokumentu: Electroscope. 2020, č. 1.
Datum vydání: 2020
Nakladatel: Západočeská univerzita v Plzni, Fakulta elektrotechnická
Typ dokumentu: článek
article
URI: http://147.228.94.30/images/PDF/Rocnik2020/Cislo1_2020/r14c1c5.pdf
http://hdl.handle.net/11025/42298
ISSN: 1802-4564
Klíčová slova: Ramanova analýza;experiment;detekce poruchy;olej;Ramanova spektroskopie
Klíčová slova v dalším jazyce: Raman analysis;experiment;fault detection;oil;Raman spectroscopy
Abstrakt v dalším jazyce: The paper reports on an experiment in the academic laboratory that aimed to detect a transformer fault by Raman spectroscopy of the transformer oil. Indicators of oil degradation (eg gases, sludge, cellulose) could not be detected. Combustion indicators (soot – graphitic particles, graphene particles, amorphous carbon) in the transformer oil were reliably detected by Raman measurements. The transformer was disassembled at the factory. It was shown that the magnetic core and electrical circuit of the transformer were irreversibly damaged and the contamination of the active parts of the transformer and the oil was massive. Two interturn short circuits were detected. It was confirmed that in the place of the coil shorts, where an electric arc burned, melting occurred of the winding conductors and of a part of the transformer core. Raman spectroscopy proved to be a useful method for rapid diagnostics of the events in a hermetically sealed transformer vessel.
Práva: © 2020 Electroscope
Vyskytuje se v kolekcích:Číslo 1 (2020)
Číslo 1 (2020)

Soubory připojené k záznamu:
Soubor Popis VelikostFormát 
r14c1c5.pdfPlný text677,17 kBAdobe PDFZobrazit/otevřít


Použijte tento identifikátor k citaci nebo jako odkaz na tento záznam: http://hdl.handle.net/11025/42298

Všechny záznamy v DSpace jsou chráněny autorskými právy, všechna práva vyhrazena.