Full metadata record
DC poleHodnotaJazyk
dc.contributor.authorRezaei, Mohsen
dc.contributor.authorTalla, Jakub
dc.contributor.authorKomrska, Tomáš
dc.contributor.authorPeroutka, Zdeněk
dc.contributor.editorPinker, Jiří
dc.date.accessioned2021-10-29T06:36:19Z
dc.date.available2021-10-29T06:36:19Z
dc.date.issued2021
dc.identifier.citation2021 International Conference on Applied Electronics: Pilsen, 7th – 8th September 2021, Czech Republic, p. 157-162.en
dc.identifier.isbn978–80–261–0972–3 (Print)
dc.identifier.isbn978–80–261–0973–0 (Online)
dc.identifier.issn1803–7232 (Print)
dc.identifier.issn1805–9597 (Online)
dc.identifier.urihttp://hdl.handle.net/11025/45585
dc.format6 s.cs
dc.format.mimetypeapplication/pdf
dc.language.isoenen
dc.publisherUniversity of West Bohemiaen
dc.rights© University of West Bohemia, 2021en
dc.subjectSingle Earth Faultcs
dc.subjectdistribuční mřížkacs
dc.subjectPetersenova cívkacs
dc.subjectproud nulové sekvencecs
dc.subjecttransformátorcs
dc.titleFour-Leg Transformer with Defined Zero Sequence Impedance for Ground Fault Compensationen
dc.typeconferenceObjecten
dc.typekonferenční příspěvekcs
dc.rights.accessopenAccessen
dc.type.versionpublishedVersionen
dc.description.abstract-translatedSingle-phase ground faults are the most common faults in medium-voltage distribution grids. High-impedance grid grounding using a special four-leg transformer is discussed in the paper. The transformer’s zero-sequence impedance differs from positive-sequence impedance and it is designed to compensate the earth faults currents in Medium Voltage (MV) distribution grids when single-phase ground fault occurs. The designed transformer can replace the traditional arc suppression coils (ASC) in the case where no distribution transformer neutral is available or distributed compensation is required. Alternatively, the transformer can operate in parallel with the ASC.en
dc.subject.translatedSingle Earth Faulten
dc.subject.translateddistribution griden
dc.subject.translatedPetersen coilen
dc.subject.translatedZero Sequence Currenten
dc.subject.translatedtransformeren
dc.type.statusPeer-revieweden
Vyskytuje se v kolekcích:Konferenční příspěvky / Conference Papers (KEV)
Konferenční příspěvky / Conference papers (RICE)
Applied Electronics 2021
Applied Electronics 2021

Soubory připojené k záznamu:
Soubor Popis VelikostFormát 
Four-Leg_Transformer_with_Defined_Zero_Sequence_Impedance_for_Ground_Fault_Compensation.pdfPlný text1,11 MBAdobe PDFZobrazit/otevřít


Použijte tento identifikátor k citaci nebo jako odkaz na tento záznam: http://hdl.handle.net/11025/45585

Všechny záznamy v DSpace jsou chráněny autorskými právy, všechna práva vyhrazena.