Full metadata record
DC pole | Hodnota | Jazyk |
---|---|---|
dc.contributor.author | Rezaei, Mohsen | |
dc.contributor.author | Talla, Jakub | |
dc.contributor.author | Komrska, Tomáš | |
dc.contributor.author | Peroutka, Zdeněk | |
dc.date.accessioned | 2022-02-07T11:00:14Z | - |
dc.date.available | 2022-02-07T11:00:14Z | - |
dc.date.issued | 2021 | |
dc.identifier.citation | REZAEI, M. TALLA, J. KOMRSKA, T. PEROUTKA, Z. Four-leg transformer with defined zero sequence impedance for ground fault compensation. In International Conference on Applied Electronics (AE 2021) : /proceedings/. Pilsen: University of West Bohemia, 2021. s. 157-163. ISBN: 978-80-261-0972-3 , ISSN: 1803-7232 | cs |
dc.identifier.isbn | 978-80-261-0972-3 | |
dc.identifier.issn | 1803-7232 | |
dc.identifier.uri | 2-s2.0-85116419417 | |
dc.identifier.uri | http://hdl.handle.net/11025/46753 | |
dc.format | 7 s. | cs |
dc.format.mimetype | application/pdf | |
dc.language.iso | en | en |
dc.publisher | University of West Bohemia | en |
dc.relation.ispartofseries | International Conference on Applied Electronics (AE 2021) : /proceedings/ | en |
dc.rights | © University of West Bohemia | en |
dc.title | Four-leg transformer with defined zero sequence impedance for ground fault compensation | en |
dc.type | konferenční příspěvek | cs |
dc.type | ConferenceObject | en |
dc.rights.access | openAccess | en |
dc.type.version | publishedVersion | en |
dc.description.abstract-translated | Single-phase ground faults are the most common faults in medium-voltage distribution grids. High-impedance grid grounding using a special four-leg transformer is discussed in the paper. The transformer’s zero-sequence impedance differs from positive-sequence impedance and it is designed to compensate the earth faults currents in Medium Voltage (MV) distribution grids when single-phase ground fault occurs. The designed transformer can replace the traditional arc suppression coils (ASC) in the case where no distribution transformer neutral is available or distributed compensation is required. Alternatively, the transformer can operate in parallel with the ASC. | en |
dc.subject.translated | single earth fault | en |
dc.subject.translated | distribution grid | en |
dc.subject.translated | petersen coil | en |
dc.subject.translated | zero sequence current | en |
dc.subject.translated | transformer | en |
dc.identifier.doi | 10.23919/AE51540.2021.9542922 | |
dc.type.status | Peer-reviewed | en |
dc.identifier.obd | 43933696 | |
Vyskytuje se v kolekcích: | Konferenční příspěvky / Conference papers (RICE) Konferenční příspěvky / Conference Papers (KEV) OBD |
Soubory připojené k záznamu:
Soubor | Velikost | Formát | |
---|---|---|---|
Rezai_Four-Leg.pdf | 1,11 MB | Adobe PDF | Zobrazit/otevřít |
Použijte tento identifikátor k citaci nebo jako odkaz na tento záznam:
http://hdl.handle.net/11025/46753
Všechny záznamy v DSpace jsou chráněny autorskými právy, všechna práva vyhrazena.