Název: | The Effect of Various Flame Retardants on Thermal Properties of Cable Insulation |
Autoři: | Prosr, Pavel Polanský, Radek Chudoba, V. Leńczyk, Lukáš |
Citace zdrojového dokumentu: | PROSR, P. POLANSKÝ, R. CHUDOBA, V. LEŃCZYK, L. The Effect of Various Flame Retardants on Thermal Properties of Cable Insulation. In Proceedings of the 2022 9th International Conference on Condition Monitoring and Diagnosis (CMD). Piscataway: IEEE, 2022. s. 454-457. ISBN: 978-4-88686-431-4 |
Datum vydání: | 2022 |
Nakladatel: | IEEE |
Typ dokumentu: | konferenční příspěvek ConferenceObject |
URI: | http://hdl.handle.net/11025/50942 |
ISBN: | 978-4-88686-431-4 |
Klíčová slova v dalším jazyce: | cables;flame retardants;thermal analyses |
Abstrakt v dalším jazyce: | Cables are used in many areas of industry. Their insulation system is mainly made of polymeric materials, so its flammable properties limit its use. For this reason, flame retardant fillers are added during production to improve heat resistance. Aluminium hydroxide (ATH - Al(OH)3) and magnesium hydroxide (MDH - Mg(OH)2) belong among the most frequently used flame retardants. Generally, flame retardancy occurs during the decomposition of these substances. The process is associated with the release of water and the absorption of heat (endothermic reaction). As the two flame retardants mentioned above have different decomposition temperatures, the properties of the resulting insulation are affected. Therefore, this paper compares the behavior of three cable insulations with different flame retardant incorporation. Simultaneous Thermal Analysis (STA), Differential Scanning Calorimetry (DSC), Dynamic Mechanical Analysis (DMA), and Fourier Transform Infrared Spectroscopy (FT-IR) were used for the comparison of samples. The results indicate the different behavior of these insulations over a wide temperature range. The evaluation was based on analyzing the glass transition temperatures, decomposition temperatures, and mechanical moduli change during thermal heating. |
Práva: | Plný text je přístupný v rámci univerzity přihlášeným uživatelům. © The Institute of Electrical Engineers of Japan |
Vyskytuje se v kolekcích: | Konferenční příspěvky / Conference papers (RICE) Konferenční příspěvky / Conference Papers (KET) OBD |
Soubory připojené k záznamu:
Soubor | Velikost | Formát | |
---|---|---|---|
Prosr_P2-10.pdf | 1,08 MB | Adobe PDF | Zobrazit/otevřít Vyžádat kopii |
Použijte tento identifikátor k citaci nebo jako odkaz na tento záznam:
http://hdl.handle.net/11025/50942
Všechny záznamy v DSpace jsou chráněny autorskými právy, všechna práva vyhrazena.