Title: Optimized protection coordination of microgrids considering power quality-based voltage indices incorporating optimal sizing and placement of fault current limiters
Authors: Azimi, Abolfazl
Hashemi Dezaki, Hamed
Citation: AZIMI, A. HASHEMI DEZAKI, H. Optimized protection coordination of microgrids considering power quality-based voltage indices incorporating optimal sizing and placement of fault current limiters. Sustainable Cities and Society, 2023, roč. 96, č. September 2023, s. nestránkováno. ISSN: 2210-6707
Issue Date: 2023
Publisher: Elsevier
Document type: článek
article
URI: 2-s2.0-85159369599
http://hdl.handle.net/11025/52995
ISSN: 2210-6707
Keywords in different language: optimal placement and sizing of fault current;limiters (FCLs);power quality voltage-based objective;voltage sag energy index (VSEI);optimal protection coordination;directional overcurrent relays (DOCRs);microgrids (MGs)
Abstract in different language: Several solutions, such as fault current limiters (FCLs), have been utilized to mitigate the challenges of smart grids and ADNs’ protection schemes. However, less attention has been paid to simultaneously optimizing the protection coordination and power quality (PQ) concerns, incorporating the FCLs. There is a research gap in the literature in developing a method for optimal placement and impedance value of FCLs to optimize the speed of the protection systems, voltage sag energy index, and voltage sag duration. This research aims to fill such a research gap by proposing a new multi-objective optimization problem based on the optimum placement and impedance value of FCL. The proposed method is examined by implementing the distribution network of the IEEE 30-bus test system. MATLAB and DIgSILENT are linked online to simulate the protection of the smart grid and PQ voltage-based analyses and find the best solutions by the genetic algorithm (GA). The comparative analyses infer that a 13.13% improvement in criteria, e.g., operating time of relays, voltage sag energy, and voltage sag duration, is achieved by optimal placement of FCLs, beside other decision variables.
Rights: Plný text je přístupný v rámci univerzity přihlášeným uživatelům
© Elsevier B.V.
Appears in Collections:Články / Articles (RICE)
OBD

Files in This Item:
File SizeFormat 
Dezaki_1-s2.0-S2210670723002457-main.pdf5,32 MBAdobe PDFView/Open    Request a copy


Please use this identifier to cite or link to this item: http://hdl.handle.net/11025/52995

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.